Owner’s
Manual
A TS Annunciator
Cat alo g 214A400, 214A401, 214A404
DANGER is used in this manual to warn of high
voltages capable of cau si n g shock , burns, or death .
WARNINGisusedinthismanualtowarn
of possible personal injury.
!
CAUTIONisusedinthismanualtowarn
of possible equipment damage.
!
Master ATS Annunciator
Catalog 214A400, 214A404
Catalog 214A401
Slave ATS Annunciator
An experien ce d licen sed electrician must install the AT S
Annunciator.
General
There are three types of ATS (Automatic Transfer
Switch) Annunciators. They are identified as follows:
Cata log 214A400 Master U nit
Cata log 214A404 Master U nit
used with a Network Supervisor
Catalog 214A401 Slave Unit
Each installation must have a master unit; each
master unit can support two s lave units. Each unit can
annunciate four ATSs. Therefore a master and two
slave units can annunciate up to twelve ATSs. To
annunciate more ATSs, additional masters and slaves
can be added.
ASCO Cata log 214A400, 214A404, a nd 214A401
ATS Annunciators are designed to provide remote
visual status reporting and push button testing of ASCO
automatic transfer switches. Each ATS must have a
Group 1*, 5, 6, or 7 Microprocessor Controller with
A ccessory 72A Serial Communication Interface Option
installed .
*No te: Group 1 Controller must have version 8 or
lower software (dash number on microprocessor).
Ratings
Nominal Input Voltage 16 V ac 50 or 60 Hz,........
or 12 or 24 V dc............
Volt-Ampere Burden 10 VA max @ 16 V ac.......
0.5 A max @ 24 V dc.......
Environmental Temperature Range ---20˚C. to +70˚C.
Transient Withstand per NEMA ICS 1---109........
Surge Withstand (SWC) IEEE Std 472---1974.......
ANSI C37.90A---1974......
Max total distance for Communication Line 4000 ft
(Master with 2 Slaves)
For greater distances contact ASCO.
Tabl e of C on t e nts
section-page
Iinstallation 1-2.............................
Setting Up the ATS Annunciator 3-5...........
Operation and ATS Testing 6................
Troubleshooting 7..........................