Emerson DC Distribution Panel User Manual

(0 Votes) | (0)
Page / 2
1087D-DistPanel / 0114
DC Distribution Panel for NetSure
Systems
Product Overview
The DC Distribution Panel for NetSure
systems is designed to provide overcur-
rent protection or separation of a single
source into multiple feeds on the output
of a DC source. This panel can be popu-
lated with up to 20 breakers and can be
wall-mounted or mounted in a 23" relay
rack. The breaker panel accepts bullet-nose style breakers from 1A to 250A. The breakers
plug into one of (20) mounting positions. Each position has a localized return landing.
Application
The DC Distribution Panel is ideal for installations where overcurrent protection or sepa-
ration of load circuits is required on the output of a rectifier or converter. This panel is
compatible with NetSure
DC power systems from Emerson or as standalone.
Additional Information
Reference spec. number 545277 for additional specification, engineering or installation
information.
LOAD RETURN
CONNECTIONS
LOAD
CONNECTIONS
5/8"
5/8"
LOAD CIRCUIT BREAKERS/FUSES
F1/
CB1
F20/
CB20
1/4-20 THREADED HOLE, 80 PLACES
1"
INPUT
3/8-16 THREADED
HOLES, 12 PLACES
INPUT
RETURN
1"
1-1/4"
1-1/4"
1-1/4"
1-1/4"
Key Features
n Flexible mounting options —
allow for relay rack or wall
mounting
n Compact panel with front
access and top feed — fits in
23" relay rack with 6U height
n Field wiring provisions, 2 hole
lug terminations — to meet
code requirements
n Bullet-nose style breakers —
provide easy installation and
removal
n Isolated Form-C alarm output
n Return bar